Service Conductors and Service Equipment in Detail
Clearances (230.24), Underground (230.30–230.33), Service-Entrance Conductors (230.40–230.54), Equipment Rules (230.62–230.82) and Service Overcurrent Protection (230.90–230.94)
NFPA 70 National Electrical Code, 2023 edition · Reviewed 2026-09-21
Lesson 02-01 covered the structure of Article 230, the number of services and the 2023 emergency-disconnect rule. This lesson fills in the sections the Georgia Class I and Class II service items actually draw from: the clearance numbers, the underground rules, the service-entrance conductor rules, the service head, the equipment sections and the supply-side connection list. Written from the 2023 text.
1. Where service conductors may go — 230.3 to 230.10
- 230.3: service conductors supplying one building shall not pass through the interior of another. 230.6 — "outside" a building means: under ≥ 2 in. of concrete beneath the building; in a raceway encased in ≥ 2 in. of concrete or brick; in a 450 Part III vault; in conduit under ≥ 18 in. of earth beneath the building; or in RMC/IMC passing through an eave (not a wall) for the 230.24 clearance.
- 230.7: other conductors (feeders, branch circuits) are not in the same raceway, cable, handhole or underground box as service conductors — except grounding electrode conductors, supply-side bonding jumpers, and load-management control conductors with OCP.
- 230.8: raceways entering from underground are sealed (spare raceways too). 230.9: open conductors 3 ft from openable windows, doors, porches, balconies, ladders, stairs and fire escapes (conductors above the top of a window excepted); the 230.24(B) vertical clearance applies within 3 ft horizontally of platforms; never beneath openings used to move materials. 230.10: no trees as supports.