Motor Circuits
Article 430 — Conductors, Overload, Short-Circuit Protection, Feeders, Controllers and Disconnects
NFPA 70 National Electrical Code, 2023 edition · Reviewed 2026-09-21
Motors and Generators is a named topic in the Wiring Methods and Materials part of the Georgia PSI outline, and motor calculations sit on both technical exams. Every motor calculation follows the same five-step chain, and every step has its own percentage. 2023 edition notes: Table 430.52(C)(1) has a separate row for Design B energy-efficient and Design B premium efficiency motors (1100 % instantaneous-trip), 430.52(C)(3) caps instantaneous-trip settings at 1300 % / 1700 %, and the small-motor 18/16 AWG rule (430.22(G)) is written around the overload relay Class. Written from the 2023 text.
1. Which current do you use? — 430.6
- Conductors, disconnect ratings and branch-circuit short-circuit/ground-fault protection: the full-load current from Tables 430.247 (dc), 430.248 (single-phase), 430.249 (two-phase) and 430.250 (three-phase) — NOT the nameplate amperes (430.6(A)(1)). If only amperes are marked, the hp is taken from the table.
- Separate overload protection: the motor NAMEPLATE current (430.6(A)(2)).
- Exceptions: multispeed motors (per winding), listed motor-operated appliances with a marked FLC (use the nameplate), low-speed/high-torque and canned-pump motors (nameplate), torque motors (nameplate), and equipment marked with MCA/MOCP (430.7(D) / 430.25).
- 430.17: the "highest rated" or "smallest rated" motor in a group is the one with the highest (or lowest) table FLC — not horsepower.
Table 430.250 (three-phase, induction) — the values that get tested:
| hp | 208 V | 230 V | 460 V |
|---|---|---|---|
| 1 | 4.6 | 4.2 | 2.1 |
| 2 | 7.5 | 6.8 | 3.4 |
| 3 | 10.6 | 9.6 | 4.8 |
| 5 | 16.7 | 15.2 | 7.6 |
| 7½ | 24.2 | 22 | 11 |
| 10 | 30.8 | 28 | 14 |
| 15 | 46.2 | 42 | 21 |
| 20 | 59.4 | 54 | 27 |
| 25 | 74.8 | 68 | 34 |
| 30 | 88 | 80 | 40 |
| 40 | 114 | 104 | 52 |
| 50 | 143 | 130 | 65 |
| 60 | 169 | 154 | 77 |
| 75 | 211 | 192 | 96 |
| 100 | 273 | 248 | 124 |
Table 430.248 (single-phase) — 115 V / 230 V: ½ hp 9.8 / 4.9; ¾ 13.8 / 6.9; 1 16 / 8.0; 1½ 20 / 10; 2 24 / 12; 3 34 / 17; 5 56 / 28; 7½ 80 / 40; 10 100 / 50.
Table 430.247 (dc, 240 V): 1 hp 4.7; 5 hp 20; 10 hp 38; 20 hp 72; 50 hp 173.